DKE German Commission for Electrical, Electronic & Information Technologies of DIN and VDE
DIN EN 60865-1
; VDE 0103:2012-09
Short-circuit currents - Calculation of effects - Part 1: Definitions and calculation methods (IEC 60865-1:2011); German version EN 60865-1:2012
Kurzschlussströme - Berechnung der Wirkung - Teil 1: Begriffe und Berechnungsverfahren (IEC 60865-1:2011); Deutsche Fassung EN 60865-1:2012
Overview
This part of the International standard series IEC 60865 is applicable to the mechanical and thermal effects of short-circuit currents. It contains procedures for the calculation of - the electromagnetic effect on rigid conductors and flexible conductors, - the thermal effect on bare conductors. For cables and insulated conductors, reference is made, for example, to IEC 60949 and IEC 60986. For the electromagnetic and thermal effects in d.c. auxiliary installations of power plants and substations reference is made to IEC 61660-2. Only three-phase and a.c. systems are dealt with in this standard. The following points should, in particular, be noted: a) The calculation of short-circuit currents should be based on IEC 60909. For the determination of the greatest possible short-circuit current, additional information from other IEC standards may be referred to, for example, details about the underlying circuitry of the calculation or details about current-limiting devices, if this leads to a reduction of the mechanical stress. b) Short-circuit duration used in this standard depends on the protection concept and should be considered in that sense. c) The standardized procedures are adjusted to practical requirements and contain simplifications which are conservative. Testing or more detailed methods of calculation or both may be used. d) In clause 5 of this standard, for arrangements with rigid conductors, only the stresses caused by short-circuit currents are calculated. Furthermore, other stresses can exist, for example, caused by dead-load, wind, ice, operating forces or earthquakes. The combination of these loads with the short-circuit loading should be part of an agreement and/or be given by standards, for example, erection-codes. The tensile forces in arrangements with flexible conductors include the effects of deadload. With respect to the combination of other loads the considerations given above are valid. e) The calculated loads are design loads without any additional partial safety factor und should be used according to installation codes of, for example, IEC 61936-1. The responsible committee is Subcommittee UK 121.2 "Mechanische und thermische Kurzschlussfestigkeit" ("Mechanical and thermal short-circuit strength") of the DKE (German Commission for Electrical, Electronic and Information Technologies) at DIN and VDE.
Document: references other documents
Responsible national committee
DKE/UK 121.2 - Mechanische und thermische Kurzschlussfestigkeit