DKE German Commission for Electrical, Electronic & Information Technologies of DIN and VDE
IEC 61200-523, TR: Electrical installation guide - Part 523: Development of simplified cable selection tables
Abstract
When designing circuits the cable and protective device have to be selected to meet safety requirements and the requirements of the load. To meet these requirements it is usual, having selected a suitable type of cable, to choose the conductor size which is as small as possible, but which will not achieve a higher temperature than the maximum permitted temperature under normal load and short circuit conditions. Requirements for meetin the thermal limits are given in IEC 60364, Chapters 43 and 52. The project concerned with the development of a simple method for selecting conductor sizes for circuits up to 125 A which meet the requirements of IEC 60364.
Begin
2001-07-20
Planned document number
IEC 64/1197/CD
Responsible national committee
DKE/K 221 - Elektrische Anlagen und Schutz gegen elektrischen Schlag
Responsible international committee
IEC/TC 64 - Electrical installations and protection against electric schock